Technical Conditions
|
Item / Type
|
JGD-1
|
JGD-2
|
JGD-3
|
Working Pressure MPa (Kg.f/cm²)
|
1 (10)
|
1,6 (16)
|
2,5 (25)
|
Bursting Pressure MPa (Kg.f/cm²)
|
2 (20)
|
3 (30)
|
4,5 (45)
|
Vacuity KPa (mmHG)
|
53,3 (400)
|
86,7 (650)
|
100 (750)
|
Application Temp. °C
|
-15 to + 115 Mannerism -30 to +250
|
Application Medium
|
Air, Compressor Air, Water, Seat Water, Hot Water, Acid, ...etc.
|
|
|
|
|
Table of main parameters of nominal core diameter, length, displacement and flange
|
DN
|
Length
|
Flange
|
Bolts
|
D. Bolt
|
D. Bolt
|
Displacement
|
Lateral
|
D. Angle
|
(mm)
|
(in)
|
L (mm)
|
b (mm)
|
n
|
d (mm)
|
D1 (mm)
|
Strech
|
Comp.
|
Displac.
|
α1+α2
|
32
|
1,25
|
95
|
16
|
4
|
18
|
100
|
6
|
9
|
9
|
15°
|
40
|
1,50
|
95
|
18
|
4
|
18
|
110
|
6
|
10
|
9
|
15°
|
50
|
2
|
105
|
18
|
4
|
18
|
125
|
7
|
10
|
10
|
15°
|
65
|
2,50
|
115
|
20
|
4
|
18
|
145
|
7
|
13
|
11
|
15°
|
80
|
3
|
135
|
20
|
8
|
160
|
160
|
8
|
15
|
12
|
15°
|
100
|
4
|
150
|
22
|
8
|
18
|
180
|
10
|
19
|
13
|
15°
|
125
|
5
|
165
|
24
|
8
|
18
|
210
|
12
|
19
|
13
|
15°
|
150
|
6
|
180
|
24
|
8
|
22
|
240
|
12
|
20
|
14
|
15°
|
200
|
8
|
210
|
24
|
8
|
22
|
295
|
16
|
25
|
22
|
15°
|
250
|
10
|
230
|
28
|
12
|
22
|
350
|
16
|
25
|
22
|
15°
|
300
|
12
|
245
|
28
|
12
|
22
|
400
|
16
|
25
|
22
|
15°
|
350
|
14
|
255
|
28
|
16
|
22
|
460
|
16
|
25
|
22
|
15°
|
400
|
16
|
255
|
30
|
16
|
26
|
515
|
16
|
25
|
22
|
15°
|
450
|
18
|
255
|
30
|
20
|
26
|
265
|
16
|
25
|
22
|
15°
|
500
|
20
|
255
|
32
|
20
|
26
|
620
|
16
|
25
|
22
|
15°
|
600
|
24
|
260
|
36
|
20
|
26
|
725
|
16
|
25
|
22
|
15°
|
700
|
28
|
320
|
36
|
24
|
30
|
840
|
16
|
25
|
22
|
15°
|
800
|
32
|
340
|
36
|
24
|
30
|
950
|
16
|
25
|
22
|
15°
|
900
|
36
|
370
|
36
|
24
|
30
|
1050
|
16
|
25
|
22
|
15°
|
1000
|
40
|
400
|
36
|
28
|
30
|
1160
|
18
|
26
|
24
|
15°
|
1200
|
48
|
420
|
36
|
32
|
33
|
1380
|
18
|
26
|
24
|
15°
|
|
|
|
|
NOTE: 1.DN32-1200PN=1MPa 2.DN32-300PN=1.6MPa 3.DN32-300PN=2.5MPa 4.Flange selected according to JB81-59 5.Special requirements may be satisfied to order by correspondence and graph. 6.When using this product for high water supply, the pipeline should be provided with fixed supports or brackets, otherwise product must be fitted with an anti-fall device. The force of fixed support or bracket should be greater than axial force, otherwise an anti-fall device is also needed.
|
|
|
|
© copyright 2011: almanit sanitary gmbh, Hamburg, Germany
|
|